Modern Low Voltage LED Luminaire Conversion Pack
With the increase in capability and popularity of LED light units Ringtail can now provide LED conversion packs to power these in emergency mode. Most LED luminaires use an external driver to power the actual LED, these low voltage drivers need special conversion packs to power it in emergency mode for the full 3 hour duration. We have provided you with two such packs that will solve your LED lamp emergency problems. Consisting of a high temperature Nickel Cadmium (NiCd) or Nickel Metal Hydride (NiMH) battery pack and converter / charger module these two units either provide constant current or constant voltage to your LED light fittings. As per traditional low voltage emergency conversions the LED conversion packs are designed to pass through the cut out of the LED in most circumstances.
Using dc-dc switcher circuitry this range provides a constant current output (CC) for use with current controlled LEDs. The ballast lumen factor is proportional to LED current, and constant throughout battery discharge. E.G. 300mA is 300/350 = 85% for a 1 watt LED.
Using dc-dc switcher circuitry this range provides a constant voltage (CV) for use with devices such as LED arrays, marker lights and LED clusters. Providing a range of 8 – 24V DC and up to 6 watts the ballast lumen factor will be 100% if the voltage is the same as the rated voltage.
The LED driver should indicate the details required to enable the selection of the correct conversion. If there is a single current rating (E.G. 700 mA) then you will need a constant current pack. If there is a single voltage rating (E.G. 12V dc) then you will need a constant voltage pack. If the voltage is shown as a range, E.G. 3-12V, the voltage is variable and therefore the current must be constant.
NOTE : Constant voltage conversions are only available as full output in emergency mode, E.G. 100% BLF. Constant current conversions however can be offered with both full output and reduced output variants, depending on the particular LED.
If you have any requirement for a conversion for an LED that is not listed above please contact our technical department for advice.